Garage Unit w/ 100A Main Switch, 6A & 16A MCBs

Stock Code: EMGUMS616

Minimum Quantity:

From ex VAT (%) VAT n/a
From inc VAT (%) VAT n/a
Call Free
Discount:
Price ex VAT (%):
Price inc VAT (%):
VAT n/a:
Product not available

The distribution equipment and consumer units designed by EXCEL GROUP LTD is fully compliant with the requirements of BS EN 61439-3 and the 18th Edition Wiring Regulations of BS 7671 IET Wiring Regulations. With multiple configurations and ranges available for customer installations

Standard Device Standard Consumer Unit BS EN 61439-3 Main Switch BS EN 60947-3 RCD BS EN 61008-1 MCB BS EN 60898-1 RCBO BS EN 61009-1 SPD BS EN 61643-11

Safety

All products must be installed by a competent electrician, giving consideration to their intended use and in accordance with the current edition of BS 7671 (IET Wiring Regulations).

The total load supplied by this unit must not exceed the rating of the main switch or RCD.

The total load of the MCBs may exceed this value where appropriate diversity is applied.

The Electricity at Work regulations and the Health and Safety at Work Act shall be complied with.

Install in the horizontal plane only.

Ambient Temperature: the MCBs fitted to this unit are calibrated at 30°C in accord with calibration temperature requirements of EN60898. At other temperatures the following rating factors should be used. 60°C: 0.85 20°C :1.0 0°C :1.15

Adjacent Thermal Magnetic MCBs should not be continuously loaded at their nominal rated currents or approach their nominal rated currents when mounted in Enclosures. It is recommended that a 60% de rating factor be applied to the MCBs nominal rated current where it is intended to load the MCB continuously.

Torque Setting Device Max Cable Capacity(mm2) Recommended Torque Main Switch 35 2.5 RCD/RCCB 35 2.5 MCB 16 2 RCBO 16 In 6 Out 2/1.2 Earth and Neutral Terminals 16 2

Warning

Before connecting to the power, check all connections (include factory made connections) are Torqued according to Torque Setting, Loose connections can cause fires!

Technical Specifications Operating Voltage (Ue) 230V Rated Insulation Voltage (Ui) 400V Rated Conditional Short Circuit Current (Icc) 16KA Rated Impulse Withstand Voltage (Uimp) 4KV Rated Current (In A) Up to 100A (except 4 module consumer unit is 63A ) Operating Frequency 50Hz IK rating Ik05 IP rating IP 4X When fitted with blanks on spare ways, IP2X when blanks not fitted Rated current of outgoing circuits (Inc) MCB: 6A-63A

RCBO: 6A-40A

RCD: 63A and 100A type A Pollution Degree 2 Usage Domestic, Indoor Use only

Name File Name
Consumer Unit Installation InstructionsData Sheet Consumer Unit Installation InstructionsData Sheet.pdf